background image

507607-03

Issue 1827

Page 11 of 23

Do not use a compressor to evacuate a system. Avoid 

deep vacuum operation. Extremely low vacuums can 

cause internal arcing and compressor failure. Danger of 

equipment damage. Damage caused by deep vacuum 

operation will void warranty.

 WARNING

Use a thermocouple or thermistor electronic vacuum 

gauge that is calibrated in microns. Use an instrument that 

reads down to 500 microns.

1.  Connect the manifold gauge set to the service valve 

ports as follows:

•  Low pressure gauge to suction line service valve
•  High pressure gauge to liquid line service valve

2.  Connect micron gauge.
3.  Connect the vacuum pump (with vacuum gauge) to 

the center port of the manifold gauge set.

4.  Open both manifold valves and start vacuum pump.
5.  Evacuate the line set and indoor unit to a minimum 

of 500 microns or lower. During the early stages of 

evacuation, it is desirable to close the manifold gauge 

valve at least once to determine if there is a rapid 

rise in pressure. A rapid rise in pressure indicates a 

relatively large leak. If this occurs, the leak testing 

procedure must be repeated.

6.  When 500 microns or lower is maintained, close the 

manifold gauge valves, turn off the vacuum pump, and 

disconnect the manifold gauge center port hose from 

the vacuum pump. Attach the manifold gauge center 

port hose to a nitrogen cylinder with pressure regulator 

set to 150 psig and purge the hose. Open the manifold 

gauge valves to break the vacuum in the line set and 

indoor unit. Close the manifold gauge valves.

7.  Shut off the nitrogen cylinder and remove the manifold 

gauge hose from the cylinder. Open the manifold 

gauge valves to release the nitrogen from the line set 

and indoor unit.

8.  Reconnect the manifold gauge to the vacuum pump, 

turn the pump on, and continue to evacuate the line 

set and indoor unit until 500 microns is maintained 

within a 20 minute period after shutting off the vacuum 

pump and closing the manifold gauge valves.

9.  When the requirements above have been met, 

disconnect the manifold hose from the vacuum pump. 

Open the service valves to break the vacuum in the 

line set and indoor unit.

Start-Up

If unit is equipped with a crankcase heater, it should 

be energized 24 hours before unit start-up to prevent 

compressor damage as a result of slugging.

 CAUTION

1.  Rotate fan to check for frozen bearings or binding.
2. 

Inspect all factory and field-installed wiring for loose 

connections.

3.  After evacuation is complete, open liquid line and 

suction line service valves to release refrigerant 

charge (contained in outdoor unit) into system.

4. 

Replace the stem caps and secure finger tight, then 

tighten an additional 1/6 of a turn.

5.  Check voltage supply at the disconnect switch. The 

voltage must be within the range listed on the unit 

nameplate. If not, do not start equipment until the 

power company has been consulted and the voltage 

condition corrected.

6.  Set thermostat for cooling demand, turn on power to 

indoor blower, and close the outdoor unit disconnect 

switch to start the unit.

7.  Recheck unit voltage with unit running. Power must be 

within range shown on unit nameplate.

Refrigerant Charging

This system is charged with R-410A refrigerant which 

operates at much higher pressures than R-22. The liquid 

line drier provided with the unit is approved for use with 

R-410A. Do not replace it with one designed for use with 

R-22. This unit is NOT approved for use with coils which 

use capillary tubes as a refrigerant metering device.

R410A refrigerant cylinders are rose colored. Refrigerant 

should be added through the suction valve in the liquid 

state.

Certain R-410A cylinders are identified as being equipped 

with a dip tube. These allow liquid refrigerant to be drawn 

from the bottom of the cylinder without inverting the 

cylinder. Do not turn this type of cylinder upside down to 

draw refrigerant. 

Units are factory charged with the amount of R410A 

refrigerant indicated on the unit rating plate. This charge is 

based on a matching indoor coil and outdoor coil with 15’ 

line set. For varying lengths of line set, refer to Table 4 for 

refrigerant charge adjustment. A blank space is provided 

on the unit rating plate to list the actual field charge.

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: