background image

507607-03

Issue 1827

Page 12 of 23

Table 4. Refrigerant Charge Adjustment

Liquid Line Set Diameter

Oz. Per 5 ft. Adjust from 15 

ft. Line Set*

3/8 in.

3 oz. per 5 ft.

* If line length is greater than 15 ft. , add this amount.  If line 

length is less than 15 ft., remove this amount.

Mineral oils are not compatible with R-410A. If oil must 

be added, it must be a polyolester oil.

 IMPORTANT

If the system is void of refrigerant, clean the system using 

the procedure described below.

1.  Use dry nitrogen to pressurize the system and check 

for leaks. Repair leaks, if possible.

2.  Evacuate the system to remove as much of the 

moisture as possible.

3.  Use dry nitrogen to break the vacuum.
4.  Evacuate the system again.
5.  Weigh the appropriate amount of R-410A refrigerant 

(listed on unit nameplate) into the system.

6.  Monitor the system to determine the amount of 

moisture remaining in the oil. Use a test kit to verify 

that the moisture content is within the kit’s dry color 

range. It may be necessary to replace the filter drier 

several times to achieve the required dryness level. If 

system dryness is not verified, the compressor will fail 

in the future.

The outdoor unit should be charged during warm weather. 

However, applications arise in which charging must occur 

in the colder months. The method of charging is determined 

by the unit’s refrigerant metering device and the outdoor 

ambient temperature.

Measure the liquid line temperature and the outdoor 

ambient temperature as outlined below:

1.  Connect the manifold gauge set to the service valve 

ports as follows:

•  Low pressure gauge to suction line service valve
•  High pressure gauge to liquid line service valve

2.  Close manifold gauge set valves. Connect the center 

manifold hose to an upright cylinder of R-410A.

3.  If room temperature is below 70°F, set the room 

thermostat to call for heat. This will create the 

necessary load for properly charging the system in the 

cooling cycle.

4.  Use a digital thermometer to record the outdoor 

ambient temperature.

5. 

When the heating demand has been satisfied, switch 

the thermostat to cooling mode with a set point of 

68°F. When pressures have stabilized, use a digital 

thermometer to record the liquid and suction line 

temperatures.

6.  The outdoor temperature will determine which 

charging method to use. Proceed with the appropriate 

charging method.

Charge  Using  Weigh-In  Method  (Fixed  Orifice/TXV 

Systems) - Outdoor Temperatures Below 65°F

If the system is void of refrigerant, or if the outdoor ambient 

temperature is cool, use the weigh-in method to charge the 

unit. Do this after any leaks have been repaired.

1.  Recover the refrigerant from the unit.

2.  Conduct a leak check, then evacuate as previously 

outlined.

3.  Weigh in the charge according to the total amount 

shown on the unit nameplate.

If weighing facilities are not available or if unit is being 

charged during warm weather, use one of the following 

procedures.

Charge  Using  Subcooling  Method  (Fixed  Orifice/TXV 

Systems) - Outdoor Temperatures 65°F or Above

If charging a fixed orifice or TXV system when the outdoor 

ambient temperature is 65°F or above, the subcooling 

method can be used to charge the unit.

1.  With the manifold gauge hose still on the liquid 

service port and the unit operating stably, use a digital 

thermometer to check the liquid line temperature. 

For best results, use the same digital thermometer 

to check both the outdoor ambient and the liquid line 

temperatures.

2.  At the same time, record the liquid line pressure 

reading.

3.  Use the temperature/pressure chart to determine the 

saturation temperature for the liquid line pressure 

reading.

4.  Subtract the liquid line temperature from the saturation 

temperature (according to the chart) to determine 

subcooling.

5.  Compare the subcooling value with those shown on 

charge label located on back of control box cover.

Charge  Using  Approach  Method  (TXV  System)  - 

Outdoor Temperatures 65°F or Above

The following procedure is intended as a general guide 

and is for use on expansion valve systems only. For best 

results, indoor temperature should be 70°F to 80°F. Monitor 

system pressures while charging.

1.  Record outdoor ambient temperature using a digital 

thermometer.

Summary of Contents for 4SCU 16 LS Series

Page 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Page 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Page 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Page 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Page 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Page 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Page 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Page 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Page 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Page 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Page 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Page 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Page 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Page 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Page 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Page 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Page 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Page 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Page 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Page 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Page 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Page 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Page 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Reviews: