Chapter 5: Technical specifications
64
1X-X3 Installation Manual
2010-1-RB output specifications
Number of outputs
Output type
Number of potential-free contacts
Current rating (when active)
Current consumption (standby)
Current consumption (active)
4 (OUT1 to OUT4)
Free-of-voltage relay
2 (normally-open NO and normally-closed NC)
2 A max. at 30 VDC
15 mA at 24 VDC
50 mA (all outputs) at 24 VDC
[1] Optional expansion board not supplied with control panel.
Table 25: Power supply equipment specifications for EN 54-4
Current consumption (Imin) [1]
0.05 A min.
Current consumption in standby (Imin a)
0.39 A max.
Current consumption in alarm (Imax b)
2.78 A max.
[1] All zones and inputs in standby, no outputs activated, no expansion boards installed, no 24V
auxiliary used and batteries fully charged.
Mechanical and environmental specifications
Table 26: Mechanical specifications
Cabinet dimensions without cover
421 × 100 × 447 mm
Weight without batteries
3.9 kg
Number of cable knockouts
20 x Ø 20 mm at top of cabinet
2 x Ø 20 mm at bottom of cabinet
26 x Ø 20 mm at rear of cabinet
IP rating
IP30
Table 27: Environmental specifications
Environmental class
Class A
Operating temperature
Storage temperature
−5 to +40ºC
−20 to +70ºC
Relative humidity
10 to 95% noncondensing
Type class conditions
3K5 of IEC 60721-3-3
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......