Chapter 3: Configuration and commissioning
1X-X3 Installation Manual
37
Display
Description
Safety door monitoring is used (on).
Safety door monitoring is not used (off).
Safety door fault delay
Use this menu to configure a delay from 10 to 90 seconds (in steps of 5 seconds)
in reporting safety door faults caused by incorrect status (open or closed). The
default setting is 30 seconds.
To configure a safety door delay:
1. Set the display as shown below, and then press Enter.
The Door Fault/Disabled LED flashes fast to indicate that the delay
configuration menu is active.
2. Select a delay value from 10 to 90 seconds using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Pressure switch type
Use this menu to configure the low pressure switch for detection of the container
pressure. Correct pressure can be either normally closed (NC) or normally open
(NO). The default setting is normally closed (NC).
To configure the pressure switch type:
1. Set the display as shown below, and then press Enter.
The Low Pressure LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......