Chapter 5: Technical specifications
60
1X-X3 Installation Manual
Zone specifications
Table 16: General zone specifications
Zone output voltage
22 VDC nominal
24 VDC max.
18 VDC min.
Current consumption (per zone)
Standby (with 32 detectors)
Standby (with end-of-line)
Standby (with end-of-line)
Short circuit
Alarm
2.6 mA max.
7.4 mA max.
4.6 mA nominal
55 mA max.
65 mA max.
Default zone configuration
Passive end-of-line
Zone termination
4.7 kΩ 5% 1/4 W end-of-line resistor
Number of detectors per zone
Aritech Dx700 series
Other detectors
20 max.
32 max. [1][2]
Number of manual call points per zone
32 max. [1]
[1] Or as defined by local standards.
[2] Provided that the detectors meet the required zone specifications given here.
Table 17: Mixed zone specifications
Resistance (per zone)
40 Ω max.
Capacitance (per zone)
500 nF max.
Nominal impedance
Detector
Manual call point
160 to 680 Ω
±
5%
100 Ω
±
5%
Detector alarm reference range
Zone voltage
Zone impedance
6.5 to 14 V
145 to 680 Ω
Manual call point alarm reference range
Zone voltage
Zone impedance
3 to 6.5 V
75 to 144 Ω
Short circuit reference range
Zone voltage
Zone impedance
< 3 V
< 55 Ω
Open circuit reference range
Zone impedance
Zone device current consumption
> 8 kΩ
≤
2.6 mA
Table 18: Automatic and manual zone specifications
Resistance (per zone)
55 Ω max.
Capacitance (per zone)
500 nF max.
Nominal impedance
100 to 680 Ω
±
5%
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......