Chapter 5: Technical specifications
1X-X3 Installation Manual
61
Detector alarm reference range
Zone voltage
Zone impedance
3 to 14 V
75 to 680 Ω
Short circuit reference range
Zone voltage
Zone impedance
< 3 V
< 55 Ω
Open circuit reference range
Zone impedance
Zone device current consumption
> 8 kΩ
≤
2.6 mA
Input and output specifications
Table 19: Input specifications
Number of inputs
8
Default input allocation
IN1 (supervised)
IN2 (supervised)
IN3 (supervised)
IN4 (non-supervised)
IN5 (supervised)
IN6 (supervised)
IN7 (supervised)
IN8 (non-supervised)
Start extinguishing manual call point
Hold extinguishing manual call point
Abort extinguishing manual call point
Manual-only mode control
Low Pressure indication
Extinguishing Agent Flow
Safety door monitoring
Remote reset
Default input end-of-line
(supervised inputs only)
15 kΩ 5% ¼ W passive end-of-line
Unsupervised inputs resistance values
Activation input value
Deactivation input value
≤
9 kΩ ±10%
> 9 kΩ ±10%
Supervised inputs resistance values
Short circuit
Active
High impedance fault
Standby
Open circuit
≤
62 Ω
> 62 Ω to 8 kΩ
> 8 kΩ to 10 kΩ
> 10 kΩ to 21 kΩ
> 21 kΩ
Control panel input current
Standby (with end-of-line)
Activated
Open circuit
Short circuit
1.2 mA nominal
5.3 mA max.
100 µA nominal
5.75 mA max.
Low pressure input impedance values
Configured as normally closed
Configured as normally open
Standby: > 62 Ω to 8 kΩ
Low pressure: > 10 kΩ to 21 kΩ
Low pressure: > 62 Ω to 8 kΩ
Standby > 10 kΩ to 21 kΩ
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......