Chapter 2: Installation
14
1X-X3 Installation Manual
EU ordinances and regulations require the use of a key switch to control access
to this function.
The remote reset is executed when the input device switches from deactivated to
activated. Refer to the topic “Input and output specifications” on page 61 for the
impedance values for this unsupervised input.
Connecting outputs
Output functionality
Each control panel has eight outputs, marked OUT1 to OUT8 on the control
panel PCB. Output functionality is shown in Table 6 below.
Table 6: Output functionality
Output Function
Type and status
OUT1
Hold extinguishing manual call point
Free-of-voltage (unsupervised switch)
Hold inactive = open
Hold active = closed
OUT2
Abort extinguishing manual call point
Free-of-voltage (unsupervised switch)
Abort inactive = open
Abort active = closed
OUT3
Manual-only mode
Free-of-voltage (unsupervised switch)
Manual-automatic = open
Manual-only = closed
OUT4
Extinguishing released
Free-of-voltage (unsupervised switch)
Released inactive = open
Released = closed
OUT5
Fire sounders
Supervised (standard)
Off = −11 VDC (supervision)
On = +24 VDC
OUT6
Extinguishing sounders
Supervised (standard)
Off = −11 VDC (supervision)
On = +24 VDC
OUT7
Extinguishing released optical warning
panels or signs
Supervised (standard)
Off = −11 VDC (supervision)
On = +24 VDC
OUT8
Extinguishing actuator
Supervised (extinguishing EOL)
Off = −11 VDC (supervision)
On = +24 VDC
Connecting free-of-voltage outputs
These outputs use the normally open (NO) and the common (C) terminals of a
relay to provide the free-of-voltage, isolated, unsupervised switch functionality.
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......