Chapter 3: Configuration and commissioning
1X-X3 Installation Manual
29
Table 10: The basic configuration menu
Display
Menu
Values
Basic default configuration
01, 02, 05, 06
Panel mode
Basic standard
Basic evacuation
Custom
Actuator delay
00 to 60 seconds
Reset disabled delay
00 to 30 minutes
Fire sounders delay
00 to 10 minutes
Fire routing delay
00 to 10 minutes
Add an expansion board
00 to 04 modules
Restore previous configuration
N/A
Restore factory configuration
N/A
Exit without saving
N/A
Exit and save
N/A
Note:
Additional menu options are available if one or more expansion boards are
installed. See “Expansion board configuration” on page 49.
Basic default configuration
Use this menu to select operating mode configuration presets.
In both basic standard and basic evacuation modes, zone detection is the same.
The extinguishing area uses Z1 and Z2 (automatic). Fire detection uses Z3
(mixed).
Available presets are shown in the table below. The default setting is 01 (Basic
standard mode, passive end-of-line).
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......