Appendix A: Configuration presets
68
1X-X3 Installation Manual
Input and output configuration
Table 28: Inputs and outputs
IN1
Start MCP
Supervised
IN2
Hold MCP
Supervised
IN3
Abort MCP
Supervised
IN4
Manual-only mode activation
Unsupervised
IN5
Low pressure indication
Supervised
IN6
Extinguishing agent flow
Supervised
IN7
Safety door fault monitor
Supervised
IN8
Remote reset
Unsupervised
OUT1
Hold MCP
Unsupervised
OUT2
Abort MCP
Unsupervised
OUT3
Manual-only mode
Unsupervised
OUT4
Extinguishing released
Unsupervised
OUT5
Fire sounders
Supervised
OUT6
Extinguishing sounders
Supervised
OUT7
Extinguishing released optical
warning panels or signs
Supervised
OUT8
Actuator
Supervised
Default delays
Table 29: Default delay configuration
Fire sounders delay
0
Fire routing delay [1]
0
Zone delay
0n
Released delay
10 seconds
[1] Requires installation of optional 2010-1-SB expansion board (not supplied).
Basic configuration modes
Basic standard mode
Fire sounders cannot be manually activated in this operating mode (fire sounders
are only activated if there is a fire alarm).
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......