Chapter 3: Configuration and commissioning
32
1X-X3 Installation Manual
The Reset LED flashes fast to indicate that the delay configuration menu is
active.
2. Select a delay value from 00 to 30 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Fire sounders delay
Use this menu to configure a fire sounders delay of up to 10 minutes. The default
setting is 00 (no delay). For more information on delay operation, see “Fire delay
operation” on page 33.
To configure a fire sounders delay:
1. Set the display as shown below, and then press Enter.
The Fire Sounders Delay LED flashes fast to indicate that the sounder delay
configuration menu is active.
2. Select a delay value from 00 to 10 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Once configured the delay must be enabled at the operator user level.
To enable a configured delay:
1. Exit the installer user level.
2. Enter the operator user level password.
3. Press the Sounder Delay button.
A steady Sounder Delay LED indicates that the delay is enabled.
Fire routing delay
Use this menu to configure a fire routing delay of up to 10 minutes. The default
setting is 00 (no delay). For more information on delay operation, see “Fire delay
operation” on page 33.
To configure a delay:
1. Set the display as shown below, and then press Enter.
Summary of Contents for 1X-X3
Page 1: ...1X X3 Installation Manual P N 501 419003 1 11 REV 01 10 ISS 11NOV13 ...
Page 6: ...iv 1X X3 Installation Manual ...
Page 26: ...Chapter 2 Installation 20 1X X3 Installation Manual ...
Page 64: ...Chapter 4 Maintenance 58 1X X3 Installation Manual ...
Page 82: ...Appendix B Regulatory information 76 1X X3 Installation Manual ...
Page 86: ...Index 80 1X X3 Installation Manual ...
Page 87: ......
Page 88: ......