User Guide
P225/EN FT/B11
MiCOM P225
Page 41/52
4.11.10 The LATCH TRIP ORDER submenu: Latching of the trip output relay
In this menu, the user selects which functions are to maintain the output relays energised
when an order is generated by these functions.
Therefore, when one of the functions set as latching issues a trip signal via output relay RL1,
the relay remains energised after the end of the trip signal. It will be necessary to come and
acknowledge the P225 in order to switch off the output relay RL1.
N.B.:
– Latching of the output relays is optional for each of these functions.
The user can chose whether to assign these functions to the “ trip
output relay latching facility ”.
– There are 3 possible ways to acknowledge the P225, and thus
switch off the output relay RL1 in the event of latching:
- press
the
"
pushbutton,
- send an acknowledge order to the configured logic input
on “ EXT RESET ”
- send a acknowledge remote order via the communication
network (order given by a supervisor)
– On loss of auxiliary power, the output relay drops back. On return
of auxiliary power, the output relay is re-energised, independently
of the fault status (still present or cleared).
4.11.11 The CB FAIL sub-menu: Breaker failure protection
The breaker failure function is used to quickly detect that a circuit-breaker has not opened
(phase fault currents still present) after a trip signal.
This function is based on a "I<BF" current threshold and on a "tBF" time-delay; these two
settings can be configured by the user.
If this function is commissioned by the user, it is activated every time relay RL1 issues a trip
command.
The "tBF" time-delay is initiated upon energisation of output relay RL1. Then, for each
phase, the MiCOM relay detects the first crossing of the current out of the zone created by
"
I
<BF". Upon detecting this crossing, the MiCOM relay initiates another time-delay with a
fixed value equivalent to 20 samples.
The relay sampling value is 32 samples/cycle. Therefore, the duration of the fixed time-
delay is 12.5ms at 50Hz and 10.4ms at 60Hz As long as this 12.5ms timer is running, the
relay checks whether the current leaves the current zone again. Where the current is not
suppressed by the circuit breaker pole, it will come out of the zone after a half cycle, ie. 16
samples (10ms at 50Hz).
The relay restarts the 20 sample timer each time it detects that the current comes out of the
preset current zone "
I
<BF".
For each 20 sample window the relay checks that when the current leaves the zone it does
so in the opposite direction to the previous crossing:
•
If there is no opposed current crossing, then the relay decides that the circuit breaker
pole is open.
•
If there is a current crossing opposed to the previous crossing, then the relay decides
that the circuit breaker pole is still close.
At the end of the tBF time-delay, the relay checks the state of each breaker pole (according
to the principle described above). If one or several poles are not open, the MiCOM relay
issues an alarm message: "CB FAIL".
Summary of Contents for MiCOM P225
Page 1: ...MiCOM P225 Motor Protection Relay Technical Guide P225 EN T B11...
Page 2: ......
Page 4: ...P225 EN T B11 Technical Guide Page 2 2 MiCOM P225 BLANK PAGE...
Page 5: ...Connection Diagrams P225 EN CO B11 MiCOM P225 CONNECTION DIAGRAMS...
Page 6: ......
Page 8: ...P225 EN CO B11 Connection Diagrams Page 2 12 MiCOM P225 BLANK PAGE...
Page 18: ...P225 EN CO B11 Connection Diagrams Page 12 12 MiCOM P225 BLANK PAGE...
Page 19: ...Technical Specifications P225 EN TD B11 MiCOM P225 TECHNICAL SPECIFICATIONS...
Page 20: ......
Page 55: ...User Guide P225 EN FT B11 MiCOM P225 USER GUIDE...
Page 56: ......
Page 109: ...Menu of the HMI P225 EN HI B11 MiCOM P225 MENU OF THE HMI...
Page 110: ......
Page 158: ...P225 EN HI B11 Menu of the HMI Page 48 48 MiCOM P225 BLANK PAGE...
Page 159: ...Maintenance P225 EN CM B11 MiCOM P225 MAINTENANCE...
Page 160: ......
Page 162: ...P225 EN CM B11 Maintenance Page 2 18 MiCOM P225 BLANK PAGE...
Page 178: ...P225 EN CM B11 Maintenance Page 18 18 MiCOM P225 PAGE BLANCHE...
Page 179: ...Communication P225 EN CT B11 MiCOM P225 COMMUNICATION...
Page 180: ......
Page 232: ...P225 EN CT B11 Communication Page 52 52 MiCOM P225 BLANK PAGE...
Page 233: ...Setting P225 EN SV B11 MiCOM P225 SETTING...
Page 234: ......
Page 250: ...P225 EN SV B11 Setting Page 16 16 MiCOM P225 BLANK PAGE...
Page 251: ...Installation Guide P225 EN IN B11 MiCOM P225 INSTALLATION GUIDE...
Page 252: ......
Page 254: ...P225 EN IN B11 Installation Guide Page 2 12 MiCOM P225 BLANK PAGE...
Page 265: ...Test Report P225 EN RS B11 MiCOM P225 TEST REPORT...
Page 266: ......
Page 268: ...P225 EN RS B11 Test Report Page 2 20 MiCOM P225 BLANK PAGE...
Page 287: ......