P225/EN FT/B11
User Guide
Page 48/52
MiCOM P225
4.12.2
The DISTURBANCE RECORD submenu
The MiCOM P225 relay offers the possibility of saving 5 disturbance records. The data are
acquired at a frequency of 32 samples per electrical cycle, ie. 1600Hz in a 50Hz system or
1920 Hz in 60Hz system, and allows for a very faithful reconstruction of the analogue
signals.
For each recording, the relays memorises
−
the 3 phase currents
−
the earth current
−
the phase-phase voltage VAC
−
the frequency
−
the state of the 6 logic inputs
−
the state of all the output relays (including the watchdog relay)
−
the date and the time
The total duration of a recording is defined by the configuration of the pre-time and post-time.
The pre-time defines the duration of the recording before the disturbance recording triggering
order, the post time defines the duration of the recording after the disturbance recording
triggering order. In all cases, the total duration of a recording cannot exceed 2.5 seconds.
P0244ENa
Duration of recording :
2,5
seconds maximum
Pre-time
Post-time
Triggering order
The triggering of a disturbance recording can be generated:
•
when a logic entry programmed on “ DIST TRIG ” is excited (see section 4.11.4.2.4
Trigging of the disturbance recording)
•
on receipt of a remote control from a supervisor on the communications network
(RS485 rear port)
•
on receipt of a remote control from MiCOM S1 support software (RS232 front port)
•
when one of the following occurs (exclusive choice):
−
instantaneous over-stepping of one of the following current thresholds:
I
>>,
I
o>,
I
o>>, V< or V> (instantaneous short-circuit, instantaneous earth fault 1st and 2nd
stages, instantaneous under- and overvoltage data respectively)
−
or when output relay RL1 is excited (relay dedicated to the tripping of the cut-off
device). The excitement of this relay can be due to the detection of an electrical
fault or to a voluntary opening order (opening remote control on the
communication network, external order relayed by one of the logic inputs).
The disturbance recordings can be retrieved:
•
either using the remote communication network (RS485 rear port)
•
or using the MiCOM S1 support software (RS232 front port)
Summary of Contents for MiCOM P225
Page 1: ...MiCOM P225 Motor Protection Relay Technical Guide P225 EN T B11...
Page 2: ......
Page 4: ...P225 EN T B11 Technical Guide Page 2 2 MiCOM P225 BLANK PAGE...
Page 5: ...Connection Diagrams P225 EN CO B11 MiCOM P225 CONNECTION DIAGRAMS...
Page 6: ......
Page 8: ...P225 EN CO B11 Connection Diagrams Page 2 12 MiCOM P225 BLANK PAGE...
Page 18: ...P225 EN CO B11 Connection Diagrams Page 12 12 MiCOM P225 BLANK PAGE...
Page 19: ...Technical Specifications P225 EN TD B11 MiCOM P225 TECHNICAL SPECIFICATIONS...
Page 20: ......
Page 55: ...User Guide P225 EN FT B11 MiCOM P225 USER GUIDE...
Page 56: ......
Page 109: ...Menu of the HMI P225 EN HI B11 MiCOM P225 MENU OF THE HMI...
Page 110: ......
Page 158: ...P225 EN HI B11 Menu of the HMI Page 48 48 MiCOM P225 BLANK PAGE...
Page 159: ...Maintenance P225 EN CM B11 MiCOM P225 MAINTENANCE...
Page 160: ......
Page 162: ...P225 EN CM B11 Maintenance Page 2 18 MiCOM P225 BLANK PAGE...
Page 178: ...P225 EN CM B11 Maintenance Page 18 18 MiCOM P225 PAGE BLANCHE...
Page 179: ...Communication P225 EN CT B11 MiCOM P225 COMMUNICATION...
Page 180: ......
Page 232: ...P225 EN CT B11 Communication Page 52 52 MiCOM P225 BLANK PAGE...
Page 233: ...Setting P225 EN SV B11 MiCOM P225 SETTING...
Page 234: ......
Page 250: ...P225 EN SV B11 Setting Page 16 16 MiCOM P225 BLANK PAGE...
Page 251: ...Installation Guide P225 EN IN B11 MiCOM P225 INSTALLATION GUIDE...
Page 252: ......
Page 254: ...P225 EN IN B11 Installation Guide Page 2 12 MiCOM P225 BLANK PAGE...
Page 265: ...Test Report P225 EN RS B11 MiCOM P225 TEST REPORT...
Page 266: ......
Page 268: ...P225 EN RS B11 Test Report Page 2 20 MiCOM P225 BLANK PAGE...
Page 287: ......