User Guide
P225/EN FT/B11
MiCOM P225
Page 37/52
4.11.4.2.7 Auxiliary 3 and auxiliary 4 data
The “ EXT3 ” and “ EXT4 ” assignments operate similarly to “ EXT1 ” and “ EXT2 ”, but when
the associated timers expire:
−
there is no alarm message,
−
the "Alarm" led is not lit,
−
an event is recorded.
4.11.4.2.8 Thermal state reset
When a logic input is assigned to the "
θ
RESET" signal, the user can reset the thermal state
value
θ
(refer to section 4.10.1), by energising this logic input.
4.11.4.2.9 Trip circuit supervision
One or two logic inputs can be set to "TRIP CIRC" so as to be used to supervise the trip
circuit (refer to section 4.11.14.1).
4.11.4.2.10 No assignment
When a logic input is programmed on “ NONE ” (None) it becomes inactive. Whether this
logic input is switched on or not, relay P225 takes no account of it.
4.11.5
The AND LOGIC EQUAT submenu: Programmable AND logic gates
The AND LOGIC EQUAT function allows the operator to programme 4 “ AND ” logic
equations, known respectively as A, B, C and D.
Each equation can be the logic “ AND ” of one, two or several items of internal logic signals
(protection or automatism functions) or external data (state of logic inputs “ EXT 1 ”,
“ EXT2 ”, “ EXT 3 ” and “ EXT4 ”) to the relay P225.
In this menu, the user constructs each of the 4 logic equations by creating logic “ AND ” gate
between several items of data. Data is assigned to a logic equation by positioning the
corresponding digit to 1. When the digit is set at 0, the data is not assigned to the
corresponding logic equation.
Examples:
You want to create 2 “ AND ” logic equations. For the first equation, you wish to implement
the “ AND ” logic of the following data:
−
time delayed earth fault 1st element (tlo>)
−
successful start (SUCCESS START)
−
logic state of one of the binary inputs (EXT1)
&
tIo>
SUCCESS START
EXT 1
P0207ENa
For the second logic equation, you wish to implement le logic “ AND ” of the following data:
−
unbalance fault 1st element (tI2>)
−
logic state of one of the binary inputs (EXT1)
&
tIi>
EXT 1
P0208ENa
Summary of Contents for MiCOM P225
Page 1: ...MiCOM P225 Motor Protection Relay Technical Guide P225 EN T B11...
Page 2: ......
Page 4: ...P225 EN T B11 Technical Guide Page 2 2 MiCOM P225 BLANK PAGE...
Page 5: ...Connection Diagrams P225 EN CO B11 MiCOM P225 CONNECTION DIAGRAMS...
Page 6: ......
Page 8: ...P225 EN CO B11 Connection Diagrams Page 2 12 MiCOM P225 BLANK PAGE...
Page 18: ...P225 EN CO B11 Connection Diagrams Page 12 12 MiCOM P225 BLANK PAGE...
Page 19: ...Technical Specifications P225 EN TD B11 MiCOM P225 TECHNICAL SPECIFICATIONS...
Page 20: ......
Page 55: ...User Guide P225 EN FT B11 MiCOM P225 USER GUIDE...
Page 56: ......
Page 109: ...Menu of the HMI P225 EN HI B11 MiCOM P225 MENU OF THE HMI...
Page 110: ......
Page 158: ...P225 EN HI B11 Menu of the HMI Page 48 48 MiCOM P225 BLANK PAGE...
Page 159: ...Maintenance P225 EN CM B11 MiCOM P225 MAINTENANCE...
Page 160: ......
Page 162: ...P225 EN CM B11 Maintenance Page 2 18 MiCOM P225 BLANK PAGE...
Page 178: ...P225 EN CM B11 Maintenance Page 18 18 MiCOM P225 PAGE BLANCHE...
Page 179: ...Communication P225 EN CT B11 MiCOM P225 COMMUNICATION...
Page 180: ......
Page 232: ...P225 EN CT B11 Communication Page 52 52 MiCOM P225 BLANK PAGE...
Page 233: ...Setting P225 EN SV B11 MiCOM P225 SETTING...
Page 234: ......
Page 250: ...P225 EN SV B11 Setting Page 16 16 MiCOM P225 BLANK PAGE...
Page 251: ...Installation Guide P225 EN IN B11 MiCOM P225 INSTALLATION GUIDE...
Page 252: ......
Page 254: ...P225 EN IN B11 Installation Guide Page 2 12 MiCOM P225 BLANK PAGE...
Page 265: ...Test Report P225 EN RS B11 MiCOM P225 TEST REPORT...
Page 266: ......
Page 268: ...P225 EN RS B11 Test Report Page 2 20 MiCOM P225 BLANK PAGE...
Page 287: ......