Name
Range
Step
Default
Description
U3 VT scaling
factor P/S U0/
SS
-
-
-
A relay feedback value; the scaling factor that is the ratio between the
U3 channel's primary and secondary voltages. This setting is only
valid if the "2LL+U3+U4" mode is selected.
U3 scaling
factor p.u. Pri
-
-
-
A relay feedback value for channel U3; the scaling factor for the
primary voltage's per-unit value. This setting is only valid if the
"2LL+U3+U4" mode is selected.
U3 scaling
factor p.u. Sec -
-
-
A relay feedback value for channel U3; the scaling factor for the
secondary voltage's per-unit value. This setting is only valid if the
"2LL+U3+U4" mode is selected.
U4 VT scaling
factor P/S U0/
SS
-
-
-
A relay feedback value; the scaling factor that is the ration between
the U4 channel's primary and secondary voltages. This setting is only
valid is the "2LL+U3+U4" mode is selected.
U4 scaling
factor p.u. Pri
-
-
-
A relay feedback value for channel U4; the scaling factor for the
primary voltage's per-unit value. This setting is only valid if the
"2LL+U3+U4" mode is selected.
U4 scaling
factor p.u. Sec -
-
-
A relay feedback value for channel U4; the scaling factor for the
secondary voltage's per-unit value. This setting is only valid if the
"2LL+U3+U4" mode is selected.
Measurements
The following measurements are available in the measured voltage channels.
Table. 5.2.2 - 26. Per-unit voltage measurements.
Name
Unit
Range
Step
Description
Voltage Ux
("UxVolt p.u.")
× U
n
0.00…500.0 0.01
The RMS voltage measurement (in p.u.) from each of the voltage channels.
Voltage Ux
TRMS
("UxVolt TRMS
p.u.")
× U
n
0.00…500.0 0.01
The TRMS voltage (inc. harmonics up to 31
st
) measurement (in p.u.)
from each of the voltage channels.
Table. 5.2.2 - 27. Secondary voltage measurements.
Name
Unit
Range
Step
Description
Secondary voltage
Ux
("Ux Volt sec")
V
0.00…500.0 0.01
The secondary RMS voltage measurement from each of the voltage
channels.
Secondary voltage
Ux TRMS
("UxVolt TRMS
sec")
V
0.00…500.0 0.01
The secondary TRMS voltage (inc. harmonics up to 31
st
) measurement
from each of the voltage channels.
Table. 5.2.2 - 28. Voltage phase angle measurements.
Name
Unit
Range
Step
Description
Ux Angle
deg
0.00…360.00
0.01
The phase angle measurement from each of the four voltage inputs.
Table. 5.2.2 - 29. Per-unit sequence voltage measurements.
Name
Unit
Range
Step
Description
Positive sequence
voltage
("Pos.seq.Volt.p.u.")
× U
n
0.00…500.0 0.01
The measurement (in p.u.) from the calculated positive sequence
voltage.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
38
© Arcteq Relays Ltd
IM00021