Table. 5.4.17 - 156. Settings of the motor status monitoring function and how they are shared by other protection functions.
Name
Range
Step
Default
Protection
functions
Description
MST LN mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
1: On
-
Set mode of MST block.
This parameter is visible only when
Allow setting of
individual LN mode is enabled in General menu.
MST LN
behaviour
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
-
-
-
Displays the mode of MST block.
This parameter is visible only when
Allow setting of
individual LN mode is enabled in General menu.
Motor Start
0: DOL
1: Star-Delta
2: Soft start
-
0: DOL
- Motor status
monitoring
- Motor start
monitoring
(Ist>; 48)
The motor starting mode selection. The user can
select between Direct On Line (DOL), Star-Delta and
Soft start in future releases.
Motor In
Scaled
0.1...40.0xI
n
0.1xI
n
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Undercurrent
(I<; 37)
- Load jam
protection
(Im>; 51M)
The motor's nominal current scaled to per unit. If the
user selects
Object In in the CT settings, this value
should be 1.00. If scaled to the CT nominal, this value
may vary.
Motor In A
0.1...5000 A
0.1 A
-
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Undercurrent
(I<; 37)
- Load jam
protection
(Im>; 51M)
The motor's nominal current in amperes.
Nominal
starting
current
0.1…40.0xI
n
0.1xI
n
6.0xI
n
- Motor status
monitoring
- Machine
thermal
overload
protection
(Tm>; 49M)
- Motor start
monitoring
(Ist>; 48)
- Load jam
protection
(Im>; 51M)
The motor's locked rotor current with the nominal
voltage. This setting is used for automatic curve
selection and calculation. Also, the nominal starting
capacity calculation is based on this value.
A
AQ
Q-M257
-M257
Instruction manual
Version: 2.07
184
© Arcteq Relays Ltd
IM00021