Figure. 5.6.1 - 155. No wiring fault but heavy unbalance.
If any of the phases exceed the
I
set
high limit setting, the operation of the function is not activated. This
behavior is applied to short-circuits and earth faults even when the fault current exceeds the
I
set
high
limit setting.
Figure. 5.6.1 - 156. Low current and heavy unbalance.
If all of the measured phase magnitudes are below the
I
set
low limit setting, the function is not activated
even when the other conditions (inc. the unbalance condition) are met.