FITOCLIMA 2500 HP
Mod. MI 271 EN / R00 23-10-2015
-26-
2.7
Installation
1)
The equipment must be installed in a clean and airy place area, with an ambient
environment temperature above 10ºC and below 26ºC.
2)
Note size and weight of equipment.
3)
Check that there is a minimum distance of 80cm between equipment and wall/ceiling or
other equipments.
4)
Check that the deck is properly levelled. If necessary, the wheels have a leveling system.
5)
Connect the humidification circuit, which is in the side of the equipment, to a salt-free
water point (demineralised), or to an osmosis systems, with an admission pressure of 1
to 6 bar (3 to 5 bar for osmosis system), and up to 10μS conductivity (micro Siemens).
In case of just one water point it is required to connect to a demineralised cylinder.