Part number 550-100-305/0916
73
AquaBalance
TM
W
ALL
M
OUNT
GAS
-
FIRED
WATER
BOILER
— C
OMBI
Boiler Manual
32
Troubleshooting
(continued)
Control diagnosis
1. The boiler control is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together with
the fault symbol (see
Table 3 or Table 4
) indicating the fault code.
2. Certain faults cause permanent boiler shutdowns (marked with the letter “
A
” see
Table 3
): to restore operation, press the RESET
button (Item 6 - Figure 64, page 50) for 1 second or RESET on the optional remote timer control if installed; if the boiler fails
to start, it is necessary to firstly eliminate the fault.
3. Other faults (indicated with the letter “
F
”, see
Table 4,
PAGE
) cause temporary shutdowns that are automatically reset as soon
as the value returns within the boiler’s normal operating range.
Protection and error conditions
1. Several checks are included to protect the boiler and its environment. Severe error will cause a lockout condition which can only
be cleared by the reset key at the boiler front panel.
2. Non severe errors faults will reset as soon as the cause of the problem disappears/corrects themselves.
3. Number of reset action is limited to 5 in 24 hours. By powering off/on, it is possible to reset this limitation: in this way, another
5 reset per 24 hour can be done.
4. Error codes can be divided in 2 groups:
a. Lock-out condition codes – “
A
” codes: (which blocks the heat demand - Press reset button for 1 second to reset)
b. Blocking condition codes – “
F
” codes: (cause temporary shutdowns that are automatically reset as soon as the value returns
within the boilers normal working range)
Lock out condition codes
Lock out condition is given with the capital “
A
” (alarm) on the status display and error code on the
temperature display. The meaning of the error numbers are as follow:
-AKESURETODETERMINETHECAUSESOFOUTAGES$ONOTLEAVETHEBOILEROPERATINGWITHOUTACOM
-
PLETEDIAGNOSIS
Table 3
h
A
vCODES
%RRORCODE $ESCRIPTION
A01 Lockout
indication
A02 &'*';<=;>?;<
A03
High limit protection: pump does not run or no
water circulation
A04
F07 repeated 3 times in the last 24 hours
A05
No frequency feedback from fan after 1 hour
A06 ?;*'*'&;<*;<@?'?;*'*'
A16
Outside sensor is not connected
A23
Nominal water pressure not reached within
maximum allowed time
A24 '?J<!?'K&&;<;<QJ@
A26
F40 repeated 3 times in the last hour
A41
Temperature sensor not or bad connected to
the pipe (CH mode)
A42
Too high difference between two CH supply water
temperature sensors
A44
Temperature sensor not or bad connected to
the pipe (DHW mode)
A61
Flame circuit error
A62
Gas valve circuit
A63
E2 prom error
A65
ADC circuit error
Abbreviation
$ESCRIPTION
ADC
Analog Digital Converter
CH
Central Heating
DHW
Domestic Hot Water
LP
X;Z@'K'=\'?&'@*^\_<'`j
LWCO
Low Water Cut Off
MMI
Machine Interface- Control Interface
OTC
Outdoor Temperature Sensor
PCB
Printed Circuit Board - Control board
PWM
Pulse width modulation - Used for
modulating pumps and motors