Figure 22
Vent and air piping materials
5SEONLYTHEMATERIALSLISTEDBELOWENSURINGTHATALLMATERIALSMEETLOCAL
CODES
see Figure 124, page 93 for part/kit numbers)
ALL
vent and air pipes require a
BIRD SCREEN at each termination
. Most kits do not include
the bird screens. Purchase bird screens separately from Weil-McLain or vent kit supplier if not
included. [Note — bird screening is integral to the 3” PVC W-M sidewall vent cap, available
for purchase from Weil-McLain. No additional screening is required.]
USE SWEEP ELBOWS FOR ALL VENT AND AIR PIPING
— DO NOT use short
radius elbows for vent or air piping. Boiler performance could be affected.
Part number 550-100-305/0916
19
AquaBalance
TM
W
ALL
M
OUNT
GAS
-
FIRED
WATER
BOILER
— C
OMBI
Boiler Manual
6 Venting/air piping — general
continued
)TEM
Material
3TANDARDSFORINSTALLATIONSIN
5NITED3TATES
0LASTICPIPINGMATERIALS
6ENTORAIRPIPING
Vent or air pipe
&
!
PVC schedule 40
ANSI/ASTM D1785
PVC-DWV schedule 40
ANSI/ASTM D2665
CPVC schedule 40
ANSI/ASTM F441
PVC & ABS pipe
cement & primer
PVC
ANSI/ASTM D2564/F656
CPVC
ANSI/ASTM F493
Polypropylene
"!"
terminations and
cement
3IMPSON$URAVENT
Obtain all materials from
M&G Simpson-Duravent
#ENTROTHERM%CO3YSTEMS)NNO&LUE®3INGLE
wall —
Obtain all materials from Centrotherm
See manufacturer’s literature for detailed information
MUST USE LOCKING COLLAR ON EVERY JOINT
!,#STAINLESSSTEELPIPINGMATERIALS
Vent pipe
AL29-4C
stainless
steel
Heat Fab, Inc. — Saf-T-Vent®
Z-Flex, Inc. — Z-Vent II
Dura-Vent — FasNSeal®
Metal-Fab, Inc. — CORR/GUARD
Certified for direct vent appliance venting
3TAINLESSSTEELBIRDSCREENSv
(purchase separately) — see Figure 124, page 93
for part numbers
DO NOT mix piping from different pipe manufac-
turers unless using adapters specifically designed
for the purpose by the manufacturer.
Every joint on
polypropylene vent piping
must
include a locking collar.
DO NOT use cellular core PVC (ASTM F891), cel-
lular core CPVC, or Radel® (polyphenolsulfone) in
venting systems.
DO NOT cover non-metallic vent pipe and fittings
with thermal insulation.
ADAPTERS
– The boiler comes with a 3”,
3-in-1 adapter as standard. This adapter allows the
installation of 3” PVC schedule 40, CPVC schedule
40, PVC-DWV schedule 40, AL29-4C stainless steel
and Polypropylene (from Simpson-Duravent only)
piping without the need for extra adapters.
It may require an adapter at terminations.
If your venting system uses Centrotherm Eco
systems InnoFlue single wall material, then an