FBL2360 Brushless DC Motor Controller Datasheet
15
Electrical Specifications
Power Stage Electrical Specifications (at 25ºC ambient)
TABLE 8.
Parameter
Measure point
Model
Min
Typ
Max
Units
Input Voltage
Ground to Vmot
All
0 (1)
60
Volts
Input continuous Max Current
Power source current
All
80
Amps
Output Voltage
Ground to U, V, W wires
All
0 (1)
60 (2)
Volts
Power Control Voltage
Ground to Power Control
wire
All
0 (1)
65
Volts
Minimum Operating Voltage
VBat or PwrCtrl wires
All
10 (3)
Volts
Over Voltage protection range
Ground to Vmot
All
5
60 (4)
63
Volts
Under Voltage protection range
Ground to Vmot
All
0
5 (4)
63
Volts
Idle Current Consumption
Vmot or PwrCtrl wires
All
50
100 (5)
150
mA
ON Resistance (Excluding
wire resistance)
Vmot to U, V or W.
Ground to U, V or W
FBL2360
2.5
mOhm
FBL2360S
1.25
mOhm
Max Current for 30s
Motor current
FBL2360
60
Amps
FBL2360S
120
Amps
Continuous Max Current
per channel
Motor current
FBL2360
40 (6)
Amps
FBL2360S
80 (6)
Amps
Current Limit range
Motor current
FBL2360
10
50 (7)
60
Amps
FBL2360S
20
100 (7)
120
Amps
Stall Detection Amps range
Motor current
FBL2360
10
60 (7)
60
Amps
FBL2360S
20
120 (7)
120
Amps
Stall Detection timeout range
Motor current
All
1
500
(8)
65000
msec
Short Circuit Detection
threshold (9)
Between Motor wires
or Between Motor wires
and ground or Between
Motor wires and Vmot
FBL2360
125(10) Amps
FBL2360S
250 (10) Amps
Motor Acceleration/
Deceleration range
Motor Output
All
100 500(11) 65000
msec
Power cable thickness
Power input and output
All
8
AWG
Note 1: Negative voltage will cause a large surge current. Protection fuse needed if battery polarity
inversion is possible
Note 2: Can be even higher because of regeneration voltage. Never inject a DC voltage from a battery or
other fixed source
Note 3: Minimum voltage must be present on VBat or Power Control wire
Note 4: Factory default value. Adjustable in 0.1V increments
Note 5: Current consumption is lower when higher voltage is applied to the controller’s VBat or PwrCtrl wires
Note 6: Estimate. Limited by case temperature. Current may be higher with better cooling
Note 7: Factory default value. Adjustable in 0.1A increments
Note 8: Factory default value. Time in ms that Stall current must be exceeded for detection
Note 9: Controller will stop until restarted in case of short circuit detection” change with “Controller will
stop until zero command given in case of short circuit detection
Note 10: Approximate value
Note 11: Factory default value. Time in ms for power to go from 0 to 100%
15
FBL2360_1691-21588-0001-D-0720