L0086, Rev. G
AMS SENSIT 3 GLASS FRONT VENDOR
6-8
1.
TEMPERATURE
– The temperature log
contains temperature measurements taken at
half-hour intervals over the previous two days.
The display shows the recording number, the
recorded temperature, and the time and date
of the recording. The log holds 96
measurements, with number 1 being the most
recent.
2.
POWER
– The power outage log records power
failure information. The display shows the
recording number, whether power went ON or
OFF, the temperature in the cabinet, and the
time and date of the recording. The log holds
10 recordings, with number 1 being the most
recent.
3.
DOOR SWITCH
– The door switch log records
door openings and closings. The display
shows the recording number, whether the door
was OPENED or CLOSED, the temperature in
the cabinet, and the time and date of the
recording. The log holds 10 recordings, with
number 1 being the most recent.
6.15 EnergySENSIT
The EnergySensit feature is a way of
reducing energy consumption. When enabled,
EnergySensit predicts periods of inactivity and
allows the internal temperature of the
merchandiser to rise, taking advantage of these
inactive times.
Essentially, by looking at past activity, the
merchandiser learns when to expect vends and
when not to and alters the internal temperature
(and hence, energy consumption) accordingly.
Less energy is used as the internal temperature is
allowed to increase.
Because of this increase in temperature, it's
not recommended for use on temperature-critical
products. Note that the EnergySensit temperature
change feature cannot be enabled while the
Health & Safety function is enabled.
6.15.1. ENABLE
The factory default is "N" for no. When set to "Y,"
EnergySensit is enabled.
NOTE:
If the Health and Safety feature is ON, the
display will show “ENERGYSENSIT OFF”
immediately after displaying “HEALTH AND
SAFETY ON.” To use EnergySensit the
Health and Safety feature must be off.
6.15.2. CLEAR HISTORY
EnergySENSIT keeps a recorded history.
The entire contents of the history can be deleted
and a new record will start at that time.
6.15.3. SET TEMP CHG
The factory default is 10° F. TEMP CHG
(temperature change) allows the user to set the
temperature change as an increase from the
original temperature set point (Refer to Section
6.5). During predicted periods of inactivity, the
merchandiser will maintain a temperature equal to
the temperature set point plus the temperature
change value. This value can be set from 1°F to
30°F.
For example, 45° chiller set point
+ 10° EnergySENSIT change
55° merchandiser temperature
6.15.4. PATT TIME
The factory default is 7 days. PATT TIME
(pattern time) is a repeating cycle or time period
that the surrounding environment experiences.
Although it can be set from 1 to 10 days, 7 days
represents the typical cycle of most environments
in the US and many other countries. In a swing-
shift type environment where employees work 4
days and then have 4 days off, set the PATT TIME
to 8.
6.15.5. HIST FACT
The factory default is 3. The HIST FACT
(historical factor) is used to determine how much
past data to use for predicting future periods of
inactivity. If set to 3, it will use data from three
pattern times. If set to 4, it will use data from 4
pattern times, and so on. It can be set from 3 to
15. The higher the number, the less likely that
someone will purchase a warmer-than-ideal
product but the energy savings won't be as great.
6.15.6. DEL TIME
The factory default is 3 hours. DEL TIME
(delay time) is the time it takes the vendible
products to warm (or cool) by the TEMP CHG
amount. Typically, a machine full of beverages will
require a greater delay time than one full of
snacks.
6.15.7. LIGHTING
This is an optional feature in EnergySensit
Note that Lighting may be used regardless of the
status of the other EnergySensit feature, or of
Health and Safety. The factory default is "N" for
No. Press the “7” key to change between No and
Yes.
Lighting uses the historical activity data to
turn the merchandiser lights off and on for the
optional fluorescent lamps, or to dimmable
brightness for the optional LED lamps. If the lights
are off and the keypad is used or credit activity is
detected, the lights will come on for three minutes.
If the lights are off and the door is opened,
the lights will come on and remain on until the
Summary of Contents for Sensit 3 39 VRM
Page 2: ...L0086 Rev H AMS SENSIT 3 GLASS FRONT VRM ...
Page 6: ...L0086 Rev H AMS SENSIT 3 GLASS FRONT VRM iv ...
Page 16: ...L0086 Rev H AMS SENSIT 3 GLASS FRONT VRM 3 4 ...
Page 38: ......
Page 46: ...L0086 Rev G AMS SENSIT 3 GLASS FRONT VRM 9 2 Figure 9 1 Typical Wiring Diagram Sheet 2 of 2 ...
Page 50: ...L0086 Rev G AMS SENSIT 3 GLASS FRONT VRM 11 2 ...
Page 52: ...L0086 Rev G AMS SENSIT 3 GLASS FRONT VRM 12 2 ...