Page 8
EWCIE Technical Manual
4.2 DIP Switch
The DIP switch (SW1) is 4-way and has the following options:
Switch 1, 2 & 3
Sets the number of amplifiers fitted
Amplifiers
SW1
SW2
SW3
1
OFF
OFF
OFF
2
OFF
OFF
ON
3
OFF
ON
OFF
4
OFF
ON
ON
5
ON
OFF
OFF
6
ON
OFF
ON
7
ON
ON
OFF
8
ON
ON
ON
Switch 4
Enables
PSU
Monitoring
(Required in standalone version)
Set On for PSU monitoring
4.3 Indicators
Steady when a fault condition is present on the EWCIE. Indicator is
latched if there is a system fault.
Steady when the EWCIE is preventing from functioning due to a
hardware fault or communications between the Front Panel Switch and
Indicator Card and the amplifier(s) has been lost. Indicator is latched.
Steady when any of the following conditions are present:
Loss of mains voltage
Loss of backup batteries
Loss of battery charger or charger voltage outside allowable range
Fault with the backup batteries – high internal resistance, high temperature, faulty connections
Otherwise the indicator is off.
Steady when there is a fault associated with the speaker circuit (short or
interruption), strobe circuit (short or interruption) or amplifier, otherwise
off.
Steady when power is available to the EWCIE, flashing when mains voltage has not been
detected, otherwise off.
Steady when the EWCIE is in the Manual mode and the EWCIE is being controlled.by an
operator. When the MANUAL MODE indicator is Off, the EWCIE is in the AUTO mode, In
the AUTO mode, the EWCIE will respond to an alarm signal from the connected fire alarm control panel.
Steady when the EWCIE has been silenced from the fire alarm control panel.
Steady when there is a fire alarm condition present on the connected fire alarm control panel.
If the EWCIE is in the AUTO mode, then the EWCIE will respond to the alarm signal as per
the amplifier digital inputs (section 5.2) and DIP switch settings (section 5.6).
Indicator flashing at ½ Hz when the alert signal has been activated as a result of the EWCIE
responding to an alarm signal (from a connected fire alarm control panel) or operation of
the ALERT control. If the EWCIE is in the TEST condition, the alert signal is NOT broadcast.
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...