EWCIE Technical Manual
4.5.3 Test
Activating the TEST control places the EWCIE into the TEST condition.
There are three different Test Modes.
Test Mode 1
:
Momentarily pressing the Test button places the EWCIE into Test Mode 1.
This test mode allows for testing the processing and indication of alarm input signals and manual
controls for ALL Emergency Zones.
All audio (Alert, Evac, live speech and recorded messages) will NOT be broadcast to any Emergency
Zones.
Test Mode 2
:
Press and hold the Test button until the buzzer sounds twice and the Test indicator flashes twice
(approx. 6 seconds) will place the EWCIE into Test Mode 2.
This test mode provides an Audible Test Tone that is broadcast to ALL Emergency Zones.
However, if a Zone Module is used, pre-selecting certain Zones by pressing the zones associated
“Speech” button allows the Audible Test tone to be sent to the selected zones only instead of All zones.
Test Mode 3
:
Press and hold the Test button until the buzzer sounds three times and the Test indicator flashes three
times (approx. 12 seconds) will place the EWCIE into Test Mode 3.
This test mode when a Zone indicator module is used, provides the ability to place certain zones into a
test state that allows the broadcasting of Alert, Evac, speech and recorded messages to the selected
zones.
To remove the EWCIE from the TEST condition, activate the TEST control (toggle function) or activate
the RESET control.
The EWCIE will only recognise the TEST control when it is NOT broadcasting any audio – including pre-
recorded messages and live speech.
The Test control is operational at access level 2.
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...