Page 55
EWCIE Technical Manual
Each amplifier can be programmed to be activated by a cause (the same as any other output in the
system).
The following dialogue box shows an instance of a cause and effect.
Zones 1, 2 and 3 will cause Amplifier 1 to operate. The amplifier will activate the Alert and Evac
tones/messages according to the DIP switch settings (section 5.6)
The Timer field in the middle of the dialogue box is an activation delay that applies to all amplifiers.
The Activation delay in the table – applies individually to an amplifier. This individual activation delay
does allow phased evacuation sequences.
For the LoopSense to be able to control when the digital inputs are set to options other than the default,
it is necessary to set the DIP switch 5, 6 and 7 to (111) and provide additional hardwired outputs to
control the inputs.
These additional outputs will need to be programmed.
13 EvacUwiz Programming Tool
The
EvacUwiz
programming tool is a Windows configuration software and is used to construct a
configuration ‘file’, suitable for ‘programming’ the Evac-U series of OWS devices (amplifiers and/or tone
generators), and for the creation and editing of relevant sound libraries, as well as for real-time
interrogation and interaction of the OWS devices. Refer to MAN3084 OWS Programming Manual for
further details.
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...