Page 24
EWCIE Technical Manual
8.2 Inputs
The Audio Line Splitter has the following inputs:
Input
Description
IN1 - IN4
(TB1)
These inputs are used to manually active the applicable Zones 1-4 when using 3
rd
party paging
consoles. (See DIP switch setting 8.5 below)
Active low input. Short to 0V to activate (non-latching).
100V in
BRD60AMP
(TB3)
Version 3 Splitter (BRD60LMU3)
For the 25W, 50W or 120W amplifiers 100V line out then EOL K2 link must be fitted to last
splitter.
For the Tone generators on 250 and 500W 100V line out then do not fit EOL K2 link.
Version 2 Splitter (BRD60LMU2)
If the ASL is being connected to the 25W, 50W or 120W amplifiers, the 100V line out from the
Amplifier (25W & 50W) or Tone Generator (120W) is to be connected here.
100V in
From TXFR
(TB4)
Version 2 splitter boards (BRD60LMU2) Only
If the ASL is being connected to the 250W or 500W amplifiers, the 100V line out from the
amplifier is to be connected here
Note:
When 3 or more (Max is 6) ASL board’s are used or the inputs are hardwired, the DIP
switch settings 0, 13, 14 and 15 are used to determine the operation of the ASL inputs (Refer to DIP switch
settings below).
8.3 Relay Output
The Audio Line Splitter has a single relay output:
Output
Description
Fault Relay
(TB2)
Fault:
No Fault:
No Power:
Relay Open (De-energised)
Relay Closed (Energised)
Relay Open (De-Energised)
Note:
When 3 or more ASL boards are used, the DIP switch settings 0, 13, 14 and 15 are used
to determine the operation of the ASL fault relay (Refer to DIP switch settings below).
8.4 Audio Line Outputs
The four split line outputs function as follows:
Zones 1-4
Provides 4 x 100VAC 100W maximum Audio Outputs.
Combined total of the four outputs should not exceed 250W.
Each output is monitored. EOL value is between 10K - 47kΩ 5% 1/3 Watt.
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...