EWCIE Technical Manual
8.5 DIP switch settings
Address DIP switch settings.
Note:
Addresses 1-4 to be used only with CAN bus monitoring.
Addresses 5 to 12 are not used.
Addresses 0, 13, 14 and 15 are used when the ASL’s inputs and fault output are hardwired (This
option is when there are 3 to 6 ASL’s required).
The table below shows the applicable settings.
Switch 1 Switch 2 Switch 3 Switch 4 Description
OFF
OFF
OFF
OFF
No CAN bus - Normal
ON
OFF
OFF
OFF
CAN bus Address 1
OFF
ON
OFF
OFF
CAN bus Address 2
ON
ON
OFF
OFF
CAN bus Address 3
OFF
OFF
ON
OFF
CAN bus Address 4
ON
OFF
ON
OFF
Address 5 – Not used
OFF
ON
ON
OFF
Address 6 - Not used
ON
ON
ON
OFF
Address 7 – Not used
OFF
OFF
OFF
ON
Address 8 – Not Used
ON
OFF
OFF
ON
Address 9 – Not Used
OFF
ON
OFF
ON
Address 10 – Not Used
ON
OFF
OFF
ON
Address 11 – Not Used
OFF
OFF
ON
ON
Address 12 – Not Used
ON
OFF
ON
ON
No CAN bus – Inverted Inputs
OFF
ON
ON
ON
No CAN bus – Inverted fault, Inverted Inputs
ON
ON
ON
ON
No CAN bus – Inverted Fault
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...