EWCIE Technical Manual
5.2 Digital Inputs
The digital input functions vary depending on the Country Standard (Region) Dip Switch 2 & 3 settings
and the setting of Dip Switches 5, 6 & 7.
Note:
These inputs can be hardwired or controlled via the Ampac Fire panel RS485
communications bus.
5.2.1 The Primary (Default) settings:
Region Dip Switches 2 & 3 Set to either AS or NZ
,
Dip Switches 5, 6 & 7 set to any state except On (1) On (1) On (1)
refer section 5.6.
Input 1(+/-)
Bell/Trigger Input (FIB)
Active high input. Tie to 24V to activate (non-
latching); 10kΩ load opens on fault;
(Connect to FireFinder and ZoneSense Plus
FACP’s Warning System Output)
Input 2
Reset
Active low input. Short to 0V to activate (non-
latching).
Input 3
Silence
Active low input. Short to 0V to activate (non-
latching).
Input 4
External Fault
Active low input. Short to 0V to activate (non-
latching).
5.2.2 The Secondary settings:
Region Dip Switches 2 & 3 Set to either AS or NZ,
Dip Switches 5, 6 & 7 must be set to On (1) On (1) On (1
) refer section 5.6.
Input 1(+/-)
Configurable see EvacUwiz Programming
Manual MAN3084
Default is Trigger Input (FIB)
Active high input. Tie to 24V to activate (non-
latching); 10kΩ load opens on fault;
(Connect to FireFinder and ZoneSense Plus
FACP’s Warning System Output)
Input 2
Configurable see EvacUwiz Programming
Manual MAN3084
Default is Evacuate
Active low input. Short to 0V to activate (non-
latching).
Input 3
Configurable see EvacUwiz Programming
Manual MAN3084
Default is Alert
Active low input. Short to 0V to activate (non-
latching).
Input 4
Configurable see EvacUwiz Programming
Manual MAN3084
Default is Custom Tone 400/450Hz @
0.5Hz
Active low input. Short to 0V to activate (non-
latching).
5.2.3 Custom setting (NZ Special):
Region Dip Switches 2 On (1) & 3 On (1) – Custom Configuration
Dip Switches 5, 6 & 7 must be set to On (1) On (1) On (1) refer section 5.6.
Input 1(+/-)
NZ Evac Sequence
Active high input. Tie to 24V to activate (non-
latching); 10kΩ load opens on fault;
(Connect to FireFinder and ZoneSense Plus
FACP’s Warning System Output)
Input 2
NZ Alert Sequence
Active low input. Short to 0V to activate (non-
latching).
Input 3
NZ School Bell
Active low input. Short to 0V to activate (non-
latching).
Input 4
NZ Lockdown Sequence
Active low input. Short to 0V to activate (non-
latching).
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...