2.1 AS4428.16:2015 MANDATORY AND OPTIONAL FUNCTIONS
The following table shows all the mandatory and optional functions included in the
Evac
U
EWCIE.
Note: The applications of these grades are specified in AS 1670.1 and AS 1670.4
Clause
number
Title
Grade 2
Grade 3
7.2
Indication of alarm signals
M
O
7.3
Alert signal (also used for non-fire emergency)
O
O
7.6
Audible indication of alarm signal reception
M
O
7.7
Delay before emergency warning condition
X
X
7.8
Phased evacuation for multi-zoned systems
M
X
7.9.1
Silencing the emergency warning condition
from the emergency detection system
O
O
7.9.2
Silencing the emergency warning condition with
a manual control
O
O
7.10.1
Reset of the emergency warning condition from
the emergency detection system
O
O
7.10.2
Reset of the emergency warning condition with
a manual control
O
O
7.11
Output to warning devices
M
O
7.12
Emergency warning condition output signal
O
O
8.3.5
Earth fault
M
¤
M
¤
8.4
System fault
M
¤
M
¤
9
Disabled condition
O
O
10
Test condition and indication
M
O
11
Automatic/manual mode control
O
O
11.2
Manual control of distributed EWCIE
O
O
12.1
Individual emergency zone controls
O
O
12.2.2
All alert control
O
O
12.2.3
All live speech
O
O
12.2.4
All evacuate control
M
O
12.4
Indication of emergency zones in the fault
warning condition
M
¤
M
¤
13
Interface to external device(s)
O
O
14
Emergency microphone
M
O
15.15
Redundant power amplifiers
O
O
LEGEND
:
M = mandatory function
O = optional function
X = shall not be provided
O
Option Included
O
Option not included
Note: The EWCIE factory default is a Grade 3 system. By configuring phased evacuation sequences with the
EvacUwiz configuration tool will change the EWCIE to a Grade 2 system.
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...