Page 22
EWCIE Technical Manual
7 Zone Indicator Module
The Zone Indicator module is used to indicate the status of the EWCIE when more than one and up to
a maximum of eight Emergency Warning Zones (8 amplifiers) have been configured in the system.
The module also allows individual zone selection for individual emergency zone announcements and
system messages (False Alarm, System Test and Lock Down).
Note:
Alert and Evac are “ALL CALL” and override the manual selection.
Figure 7: Zone Indicator Module
Note:
Use LAB3134 editable slip in label for custom Zone Descriptions
7.1 Connectors
CN1
CAN BUS communication and power to and from the Front Panel Switch and Indicator Module
CN2
CAN BUS communication and power to and from the Amplifiers
7.2 Indicators and Controls
On steady when the associated emergency zones are in the Alert condition.
On steady when the associated emergency zones are in the Evacuate condition.
On steady when the associated emergency zones are in the Alarm (Evacuate or Alert) condition.
Flashes when the associated emergency zone is in fault. On steady when the associated emergency
zone is in the test condition.
Emergency zone “Speech” (Toggle) selection switches are used to manually select the
individual emergency zones to communicate to when using the PTT microphone on the Front
Control & Indicator module.
Additionally, the switch allows for system messages (False Alarm, System Test and Lockdown) to be played
to individual emergency zones.
If no zones are selected the PTT operates as an ALL CALL microphone and all emergency zones will be turned
on for speech.
The Speech LED is on steady when the associated emergency zone has been selected.
Note:
Pressing the buzzer silence control for 3s or longer on the Front Panel Control and Indicator Module
will initiate a Lamp Test on the Zone Indicator Module. During the Lamp Test, all indicators shall go
steady
Summary of Contents for EvacU
Page 6: ...Page 5 EWCIE Technical Manual Figure 1 Typical EWCIE System ...
Page 31: ...Page 30 EWCIE Technical Manual Figure 12 Standalone 3 x 50W with 10Amp PSU shown ...
Page 38: ...Page 37 EWCIE Technical Manual 10 9 6050 0008 EvacU Standalone 50W System Drawing ...
Page 40: ...Page 39 11 2 FireFinder plus 25W and 50W ...
Page 41: ...Page 40 11 3 LoopSense 25W and 50W ...
Page 43: ...Page 42 11 5 Multiple Amplifiers LoopSense FireFinder Plus ...
Page 44: ...Page 43 11 6 Multiple Amplifiers FireFinder ...
Page 45: ...Page 44 11 7 25W and 50W Amplifier with optional Audio Line Splitter ...