PROGRAMMING
11
The display will show:
Set the low air alarm. To do so, press
or
to change the flashing
value representing degrees Fahrenheit. If the air temperature goes below this set
point, the alarm will go off. You can set low air alarm anywhere between -30
0
F
and 50
0
F.
Press
when done.
(Default value for coolers)
(Default value for freezers)
The display will show:
Set the alarm time delay. To do so, press
or
to change the
flashing value representing minutes.
If the air temperature goes out of the preset limits the alarm will go off only after
the time set here elapses. The alarm time delay can be set anywhere between 0
(no delay) and 60 minutes. Press
when done.
The display will show:
Light Off Delay
Next, the controller will prompt you to set the automatic light off delay.
The automatic light off delay is the elapsed time between the moment the user turns the light on and the
moment the controller will automatically turn it off.
Set the automatic light off delay by pressing
or
to change the flashing value representing
minutes. The automatic light off delay can be set between 1 and 60 minutes. In case you do not want an
automatic light off delay, set this function to “
∞
”.
Press
when done.
The display will show: