SMD23E2 and SMD24E2 User Manual
ADVANCED MICRO CONTROLS INC.
58
Homing Profiles (continued)
Profile with Backplane_Proximity_Bit
Figure R4.2 below shows the move profile generated by a CW Find Home command when you use the Home
Input with Backplane_Proximity_Bit.
Figure R4.2 Homing with Proximity
1) Acceleration from the configured Starting Speed to the Programmed Speed
2) Run at the Programmed Speed
3) Ignores the Home Input because Backplane_Proximity_Bit has not made a 0
1 transition.
4) Deceleration towards the Starting Speed when the Backplane_Proximity_Bit transitions from 0 to 1.
The axis will stop as soon as the Home Input becomes active.
5) The Starting Speed is the minimum speed the profile will run at. If the axis decelerates to the Starting
Speed before reaching the Home Input, it will continue at this speed.
Figure R4.2 shows the Backplane_Proximity_Bit staying active until the SMD23E2 or
SMD24E2 reaches its home position. This is valid, but does not have to occur. As stated in
step 4, the unit starts to hunt for the home position as soon as the Backplane_Proximity_Bit
makes a 0
1 transition
(CW)
(CCW)
S
P
E
E
D
POSITION
Home
Proximity Bit
Active
Home
Input
Home Input
Summary of Contents for SMD23E2 Series
Page 10: ...ABOUT THIS MANUAL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 10 Notes...
Page 44: ...MOTION CONTROL SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 44 Notes...
Page 54: ...CALCULATING MOVE PROFILES SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 54 Notes...
Page 88: ...COMMAND MODE DATA FORMAT SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 88 Notes...
Page 128: ...MODBUS TCP CONFIGURATION SMD23E2 and SMD24E2 User Manual ADVANCED MICRO CONTROLS INC 128 Notes...
Page 134: ...LEADERS IN ADVANCED CONTROL PRODUCTS ADVANCED MICRO CONTROLS INC...