Supervisor 5000 Installation Instructions
PUD3667R1-6
For assistance: [email protected] +1 (909) 591-8431
Page 23
Post-Installation Functions Check
Alvarado turnstiles are thoroughly inspected and tested for proper performance prior to being shipped. Perform the following
function checks to verify the turnstiles have been installed properly and are fully operational. If any problems are encountered
during the functions check, refer to the Troubleshooting section on Page 31.
Before beginning the Post-Installation Functions Check, please read the following brief descriptions of the three SU5000 passage
modes. More information on SU5000 passage modes can be found in the
SU5000 User Guide
.
There is a power key switch on the inside of the base cover of all master
and center cabinets.
1. Turn on AC power using the power key switch [Figure 27]. The
power-up cycle will take less than one minute to complete.
2. After the power-up sequence has completed, the SU5000 barriers
will move to the Home position and the SU5000 will enter into
Controlled Passage mode, for both the entry and exit directions.
Fig. 27
2.5A (slo-blo) Fuse
F1
POWER OFF
POWER ON
Barriers are pre-aligned at the factory. However, they may need slight
adjustment after installation. Refer to Appendix A on Page 32 for
instructions on setting the barrier Home position.
The keys to power the turnstile ON/OFF are packaged in the hardware
box that was shipped with the turnstile.
Powering On
Passage Modes
Power Key Switch
(Flashing)
Passage Mode
Description
User Status
Display
Open / Closed
Status Light
Controlled Passage
The barriers are closed, securing the
turnstile. Upon receipt of an authorization
signal from an access control system the
barriers move away from the user to the
open position, allowing a single passage in
the authorized direction. The barriers will
close after the user has passed through the
turnstile or the time delay reset (6 second
default) has expired.
This is the default
passage mode the SU5000s are set to
before leaving the factory.
Free Passage
An access control authorization signal is
not required for a user to pass through the
turnstile. Barriers are closed until a user
enters the turnstile at which time the barriers
automatically open in the direction of travel.
The barriers will close after the user has
passed through the turnstile or the time delay
reset (6 second default) has expired.
No Passage
No passage is allowed. The barriers are
closed and remain closed. Valid electronic
credentials are ignored and passage is not
allowed. The barriers will still open in the exit
direction if a fire alarm or life safety input is
received.
NOTE
NOTE