Maintenance and Troubleshooting
99
110036 FLASH ID Alarm
1. Restart the system and check whether
the fault persists.
2. If it persists, please contact the customer
service center for further check.
Error
No.
Error Description
Solution
110037 ReadFlash Alarm
1. Restart the system and check whether
the fault persists.
2. If it persists, please contact the customer
service center for further check.
110039 Machine Type Alarm
The model in the firmware code does not
match the physical model, please contact
customer service for further check.
110040 Inv Volt Low Alarm
1. If it occurs in weak light conditions (such
as early morning or dusk, and extreme
weather such as rain and sandstorms), it is
a normal phenomenon that the compo-
nent voltage is low at this time, and no
need to deal with it..
2. If it occurs under the condition that the
light is normal, please check whether there
is a short circuit or open circuit in the solar
panel string connection.
110048 No Pv Input Alarm
1. If the alarm occurs occasionally, possibly
the external circuits are abnormal acci-
dentally. The inverter automatically recov-
ers to the normal operating status after the
fault is rectified.
2. If the alarm occurs repeatedly or last a
long time, check whether the insulation re-
sistance against the ground of solar panel
strings is too low.