Publication 2711P-UM001B-EN-P
6-14
Terminal Connections
DHPlus Network Connections
Use the Belden 9463 twin axial cable (1770-CD) to connect a
PanelView Plus terminal to the DH+ link.
You can connect a DH+ link in 2 ways:
•
trunk line/drop line - from the drop line to the connector screw
terminals on the DH+ connectors of the processor
•
daisy chain - to the connector screw terminals on the DH+
connectors on the processor
Follow these guidelines when installing DH+ communication links:
•
do not exceed these cable lengths:
–
trunk line-cable length: 3,048 m (10,000 ft)
–
drop-cable length: 30.4 m (100 ft)
The maximum cable length is determined by baud rate.
•
do not connect more than 64 stations on a single DH+ link
Logic Controller
PanelView Plus 700-1500
82 or 150 Ohm Terminating Resistor
Clear 1
Shield SH 2
Blue 3
Clear 1
Shield SH 2
Blue 3
Belden
Ferrite
PanelView Plus 400-600
Clear 1
Shield SH 2
Blue 3
Clear 1
Shield SH 2
Blue 3
Logic Controller
82 or 150 Ohm Terminating Resistor
DH+ Port on Communication Module
DH+ Port on Communication Module
82 or 150 Ohm Terminating Resistor