Publication 2711P-UM001B-EN-P
6-12
Terminal Connections
DH-485 Network Port Wiring (700 - 1500 only)
Use these instructions for wiring Belden cable. If you are using
standard Allen-Bradley cables, see the Cable section on page 6-2.
Attaching RS-485 Connector to the Communication Cable
Attach the connector to the Belden #3106A or #9842 Cable as shown
below.
The table below shows connections for Belden #3106A.
IMPORTANT
A daisy-chained network is recommended. We do
not recommend the following.
For this Wire/Pair
Connect this Wire
To this Terminal
Shield/Drain
Non-jacketed
Terminal 2 - Shield
Blue
Blue
Terminal 3 - (Common)
White/Orange
White with Orange Stripe
Terminal 4 - (Data B)
Orange with White Stripe
Terminal 5 - (Data A)
Belden
#3106A or
#9842
Belden
#3106A or
#9842
Belden
#3106A or
#9842
Connector
Connector
Connector
Incorrect
Orange with White Stripes
White with Orange Stripes
Shrink Tubing
Recommended
Blue (#3106A) or
Blue with White Stripes (#9842)
Drain Wire
6 Terminal
5 A
4 B
3 Common
2 Shield
1 Chassis Ground
Single Cable Connection
to Previous Device
to Successive Device
Multiple Cable Connection
Ferrite
Ferrite
Ferrite
Summary of Contents for PanelView Plus 2711P
Page 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Page 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Page 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Page 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Page 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Page 169: ...AB Drives...