
Publication 2711P-UM001B-EN-P
Terminal Connections
6-7
Modem Connection
Wire or radio modem communications is possible between the
PanelView Plus and controller. Each modem must support full duplex
communications. Refer to your modem user manual for details on
settings and configuration.
Constructing a Null Modem Cable
To construct a null modem cable, refer to the following pinout:
9-pin
25-pin
9-pin
3
3
3
2
2
2
5
7
5
1
8
1
4
20
4
6
6
6
8
5
8
7
4
7
DF1 Port
Optical Isolator
Modem
Modem
Controller
PanelView Plus
Summary of Contents for PanelView Plus 2711P
Page 1: ...PanelView Plus Operator Terminals 2711P 400 600 700 1000 1250 1500 User Manual AB Drives...
Page 6: ...Publication 2711P UM001B EN P Table of Contents iv...
Page 112: ...Publication 2711P UM001B EN P 5 22 Installing and Replacing Components...
Page 154: ...Publication 2711P UM001B EN P 8 16 Troubleshooting and Maintenance...
Page 160: ...Publication 2711P UM001B EN P B 2 Compatible USB Devices...
Page 169: ...AB Drives...