Input Specifications
Electrical /EMC:
The module has passed testing at the following
levels:
•
ESD Immunity
(EN61000-4-2)
•
4 kV contact, 8 kV air, 4 kV indirect
•
Radiated Immunity
(EN61000-4-3)
•
10 V/m , 80 to 1000 MHz, 80% amplitude
modulation, +900 MHz keyed carrier
•
Fast Transient Burst
(EN61000-4-4)
•
2 kV, 5kHz
•
Surge Immunity
(EN61000-4-5)
•
1kV galvanic gun
•
Conducted Immunity
(EN61000-4-6)
•
10V, 0.15 to 80MHz
(1)
(2)
(1) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30
to 1000 MHz.
(2) For grounded thermocouples, the 10V level is reduced to 3V.
Specification
Value
Specification
Value
Number of Inputs
4 input channels plus 1 CJC sensor
Resolution
15 bits plus sign
Bus Current Draw (max.)
40 mA at 5V dc
50 mA at 24V dc
Heat Dissipation
1.5 Total Watts (The Watts per point, plus the minimum
Watts, with all points energized.)
Converter Type
Delta Sigma
Response Speed per Channel
Input filter and configuration dependent. See “Effects of
Filter Frequency on Noise Rejection” on page 3-10
Rated Working Voltage
(1)
(1) Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including
the input signal and the value that floats above ground potential (for example, 30V dc input signal and 20V dc
potential above ground).
30V ac/30V dc
Common Mode Voltage Range
(2)
(2) For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common.
±10V maximum per channel
Common Mode Rejection
115 dB (minimum) at 50 Hz (with 10 Hz or 50 Hz filter)
115 dB (minimum) at 60 Hz (with 10 Hz or 60 Hz filter)
Normal Mode Rejection Ratio
85 dB (minimum) at 50 Hz (with 10 Hz or 50 Hz filter)
85 dB (minimum) at 60 Hz (with 10 Hz or 60 Hz filter)
Maximum Cable Impedance
25
Ω (
for specified accuracy)
Input Impedance
>10M
Ω
Open-circuit Detection Time
7 ms to 1.515 seconds
(3)
(3) Open-circuit detection time is equal to the module scan time, which is based on the number of enabled
channels, the filter frequency of each channel, and whether cyclic calibration is enabled..
Calibration
The module performs autocalibration upon power-up
and whenever a channel is enabled. You can also
program the module to calibrate every five minutes.
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...