Publication 1762-UM002A-EN-P - July 2002
2-12
Installation and Wiring
To wire your module follow these steps.
1.
At each end of the cable, strip some casing to expose the
individual wires.
2.
Trim the signal wires to 2-inch (5 cm) lengths. Strip about 3/16
inch (5 mm) of insulation away to expose the end of the wire.
3.
At one end of the cable, twist the drain wire and foil shield
together, bend them away from the cable, and apply shrink
wrap. Then earth ground at the preferred location based on the
type of sensor you are using. See Grounding on page 2-8.
4.
At the other end of the cable, cut the drain wire and foil shield
back to the cable and apply shrink wrap.
5.
Connect the signal wires to the terminal block. Connect the
other end of the cable to the analog input device.
6.
Repeat steps 1 through 5 for each channel on the module.
ATTENTION
!
Be careful when stripping wires. Wire
fragments that fall into a module could cause
damage at power up.
TIP
See Appendix D
Using Thermocouple Junctions
for additional information on wiring grounded,
ungrounded, and exposed thermocouple types.
cable
signal wire
signal wire
drain wire
foil shield
signal wire
signal wire
Cut foil shield
and drain wire
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...