1
Publication 1762-UM002A-EN-P - July 2002
Chapter
3
Module Data, Status, and Channel
Configuration
After installing the 1762-IT4 thermocouple/mV input module, you
must configure it for operation using the programming software
compatible with the controller (for example, RSLogix 500). Once
configuration is complete and reflected in the ladder logic, you need
to operate the module and verify its configuration.
This chapter contains information on the following:
•
module memory map
•
accessing input image file data
•
configuring channels
•
determining effective resolution and range
•
determining module update time
Module Memory Map
The module uses six input words for data and status bits (input
image), and five configuration words.
Accessing Input Image File
Data
The input image file represents data words and status words. Input
words 0 through 3 hold the input data that represents the value of the
analog inputs for channels 0 through 3. These data words are valid
only when the channel is enabled and there are no errors. Input
words 4 and 5 hold the status bits. To receive valid status information,
the channel must be enabled.
You can access the information in the input image file using the
programming software data files input screen.
Channel 0 Data Word
Word 0
Word 1
Word 2
Word 3
Word 4, bits 0 to 4 and 8 to 12
Word 5, bits 6 to 15
Channel 1 Data Word
Channel 2 Data Word
Channel 3 Data Word
General/Open-Circuit Status Bits
Over-/Under-range Bits
Input Image
6 words
slot e
Input Image
File
Memory Map
Bit 15
Bit 0
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...