Publication 1762-UM002A-EN-P - July 2002
Module Data, Status, and Channel Configuration
3-33
Determining Module
Update Time
The module update time is defined as the time required for the
module to sample and convert the input signals of all enabled input
channels and provide the resulting data values to the processor.
Module update time can be calculated by adding the sum of all
enabled channel’s times. The module sequentially samples the
enabled channels in a continuous loop as shown below.
Table 3.4 Effective Resolution vs. Input Filter Selection for Millivolt Inputs
Filter Frequency
±50mV
±100mV
10 Hz
6
µ
V
6
µ
V
50 Hz
9
µ
V
12
µ
V
60 Hz
9
µ
V
12
µ
V
250 Hz
125
µ
V
150
µ
V
500 Hz
250
µ
V
300
µ
V
1 kHz
1000
µ
V
1300
µ
V
TIP
The resolutions provided by the filters apply to the
raw/proportional data format only.
No Thermocouple
Calibration Not Active
Sample
Channel 0
Sample
Channel 1
Sample
Channel 2
Sample
Channel 3
Enabled
Enabled
Enabled
Enabled
TC Enabled
Sample
CJC
Calibration
Active
Perform
Calibration
Channel 3 Disabled
Channel 0 Disabled
Channel 1 Disabled
Channel 2 Disabled
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...