
Publication 1762-UM002A-EN-P - July 2002
2-6
Installation and Wiring
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or
1492-EAH35) for environments with vibration or shock concerns.
Panel Mounting
Use the dimensional template shown below to mount the module.
The preferred mounting method is to use two M4 or #8 panhead
screws per module. M3.5 or #6 panhead screws may also be used, but
a washer may be needed to ensure a good ground contact. Mounting
screws are required on every module.
TIP
For environments with extreme vibration and
shock concerns, use the panel mounting method
described below, instead of DIN rail mounting.
End Anchor
End Anchor
90
(3.54)
100
(3.94)
40.4
(1.59)
40.4
(1.59)
14.5
(0.57)
For more than 2 modules: (number of modules - 1) x 40.4 mm (1.59 in.)
NOTE:
Hole spacing tolerance:
±0.4 mm (0.016 in.).
Mi
cr
oLo
gi
x 1
200
Expa
nsi
on I/O
M
icr
oL
ogi
x 1200
Mi
cr
oLo
gi
x 1
200
Expa
nsi
on I/O
Mi
cr
oLo
gi
x 1
200
Expa
nsi
on I/O
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...