1
Publication 1762-UM002A-EN-P - July 2002
Appendix
A
Specifications
General Specifications
Specification
Value
Dimensions
90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm
3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width)
height including mounting tabs is 4.33 in.
Approximate Shipping Weight
(with carton)
220g (0.53 lbs.)
Storage Temperature
-40°C to +85°C (-40°F to +185°F)
Operating Temperature
0°C to +55°C (32°F to +131°F)
Operating Humidity
5% to 95% non-condensing
Operating Altitude
2000 meters (6561 feet)
Vibration
Operating: 10 to 500 Hz, 5G, 0.030 in. peak-to-peak
Relay Operation: 2G
Shock
Operating: 30G, 11 ms panel mounted
(20G, 11 ms DIN rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN rail mounted)
Non-Operating: 40G panel mounted
(30G DIN rail mounted)
Recommended Cable
Belden™ 8761 (shielded) for millivolt inputs
Shielded thermocouple extension wire for the
specific type of thermocouple you are using. Follow
thermocouple manufacturer’s recommendations.
Agency Certification
•
C-UL certified (under CSA C22.2 No. 142)
•
UL 508 listed
•
CE compliant for all applicable directives
•
C-Tick marked for all applicable acts
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A,
B, C, D
(UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions
EN50081-2 Class A
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...