Publication 1762-UM002A-EN-P - July 2002
3-12
Module Data, Status, and Channel Configuration
Channel Cut-Off Frequency
The filter cut-off frequency, -3 dB, is the point on the frequency
response curve where frequency components of the input signal are
passed with 3 dB of attenuation. The following table shows cut-off
frequencies for the supported filters.
All input frequency components at or below the cut-off frequency are
passed by the digital filter with less than 3 dB of attenuation. All
frequency components above the cut-off frequency are increasingly
attenuated as shown in the graphs on page 3-13.
Table 3.3 Filter Frequency versus Channel Cut-off Frequency
Filter Frequency
Cut-off Frequency
10 Hz
2.62 Hz
50 Hz
13.1 Hz
60 Hz
15.7 Hz
250 Hz
65.5 Hz
500 Hz
131 Hz
1 kHz
262 Hz
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...