Publication 1762-UM002A-EN-P - July 2002
Module Configuration Using MicroLogix 1200 and RSLogix 500
E-7
Configuration Using
RSLogix 500 Version 5.2 or
Lower
If you do not have version 5.5 or higher of RSLogix 500, you can still
configure your module, using the Generic Extra Data Configuration
dialog.
The 1762-IT4 uses six 16-bit binary numbers to configure each of its
four channels. To properly configure and enable input channel 1 for
the setting in the table below, add the decimal values given to each of
the six parameters. These decimal values are listed in the
configuration table on page 3-5
Enter this value into the Generic Extra Data Config tab.
Table 5.2 1762-IT4 Parameter Decimal Values
Parameter
Setting
Decimal Value
Filter Frequency
250 Hz
3
Open Circuit
Hold Last State
64
Temperature Units
Degrees F
128
Input Type
Thermocouple S
1280
Data Format
Engineering Units x 10
16384
Enable Channel
Enable
-32768
Total -14909