Diagnostics and Troubleshooting
4-3
Power-up Diagnostics
At module power-up, a series of internal diagnostic tests are
performed. If these diagnostic tests are not successfully completed,
the module status LED remains off and a module error is reported to
the controller.
Channel Diagnostics
When an input channel is enabled, the module performs a diagnostic
check to see that the channel has been properly configured. In
addition, the channel is tested on every scan for configuration errors,
over-range and under-range, and open-circuit conditions.
Invalid Channel Configuration Detection
Whenever a channel configuration word is improperly defined, the
module reports an error. See pages 4-4 to 4-6 for a description of
module errors.
Over- or Under-Range Detection
Whenever the data received at the channel word is out of the defined
operating range, an over-range or under-range error is indicated in
input data word 5.
Possible causes of an out-of-range condition include:
•
The temperature is too hot or too cold for the type of
thermocouple being used.
•
The wrong thermocouple is being used for the input type
selected, or for the configuration that was programmed.
•
The input device is faulty.
•
The signal input from the input device is beyond the scaling
range.
If module status
LED is:
Indicated
condition:
Corrective action:
On
Proper Operation
No action required.
Off
Module Fault
Cycle power. If condition persists, replace the
module. Call your local distributor or Rockwell
Automation for assistance.
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...