Publication 1762-UM002A-EN-P - July 2002
4-6
Diagnostics and Troubleshooting
Error Codes
The table below explains the extended error code.
Table 4.3 Extended Error Codes
Error Type
Hex
Equivalent
(1)
Module
Error
Code
Extended Error
Information
Code
Error Description
Binary
Binary
No Error
X000
000
0 0000 0000
No Error
General Common
Hardware Error
X200
001
0 0000 0000
General hardware error; no additional information
X201
001
0 0000 0001
Power-up reset state
Hardware-Specific
Error
X300
001
1 0000 0000
General hardware error; no additional information
X301
001
1 0000 0001
Microprocessor hardware error
X302
001
1 0000 0010
A/D Converter error
X303
001
1 0000 0011
Calibration error
Module-Specific
Configuration
Error
X400
010
0 0000 0000
General configuration error; no additional information
X401
010
0 0000 0001
Invalid input type selected (channel 0)
X402
010
0 0000 0010
Invalid input type selected (channel 1)
X403
010
0 0000 0011
Invalid input type selected (channel 2)
X404
010
0 0000 0100
Invalid input type selected (channel 3)
X405
010
0 0000 0101
Invalid filter selected (channel 0)
X406
010
0 0000 0110
Invalid filter selected (channel 1)
X407
010
0 0000 0111
Invalid filter selected (channel 2)
X408
010
0 0000 1000
Invalid filter selected (channel 3)
X409
010
0 0000 1001
Invalid format selected (channel 0)
X40A
010
0 0000 1010
Invalid format selected (channel 1)
X40B
010
0 0000 1011
Invalid format selected (channel 2)
X40C
010
0 0000 1100
Invalid format selected (channel 3)
X40D
010
0 0000 1101
An unused bit has been set for channel 0
X40E
010
0 0000 1110
An unused bit has been set for channel 1
X40F
010
0 0000 1111
An unused bit has been set for channel 2
X410
010
0 0001 0000
An unused bit has been set for channel 3
X411
010
0 0001 0001
Invalid module configuration register
(1) X represents the “Don’t Care” digit.
Summary of Contents for MicroLogix 1200
Page 1: ...MicroLogix 1200 Thermocouple mV Input Module Catalog Number 1762 IT4 User Manual AB Parts...
Page 10: ...Publication 1762 UM002A EN P July 2002 Preface 4...
Page 68: ...Publication 1762 UM002A EN P July 2002 3 38 Module Data Status and Channel Configuration...
Page 76: ...Publication 1762 UM002A EN P July 2002 4 8 Diagnostics and Troubleshooting...
Page 143: ...AB Parts...