148
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
Figure 54 - Skip Frequency Band
DCBrakeTime
Sets the length of time that DC brake current is
injected into the motor. Refer to Parameter 76
(DCBrakeLevel).
Parameter Number
75
Related Parameters
32, 76
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x secs
Minimum Value
0.0
Maximum Value
99.9
(Setting of 99.9 = Continuous)
Default Value
0.0
DCBrakeLevel
Defines the maximum DC brake current, in amps,
applied to the motor when Parameter 32
(StopMode) is set to either
0 = RAMP or 2 = DC BRAKE.
For 0.5 Hp units – Min = 0; Max = 2.7; Default = .1
For 1.0 Hp units – Min = 0; Max = 4.5; Default = .1
For 2.0Hp units – Min = 0; Max = 7.5; Default = .2
Parameter Number
76
Related Parameters
32, 75
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x Amps
Minimum Value
0.0
Maximum Value
Hp Dependant
Default Value
Hp Dependant
Frequency
Time
Skip Frequency
Command
Frequency
Drive Output
Frequency
2x Skip
Frequency Band
Summary of Contents for ArmorStart 290E
Page 1: ...ArmorStart LT Distributed Motor Controller Catalog Numbers 290E 291E 294E User Manual ...
Page 8: ...8 RockwellAutomationPublication290E UM001B EN P June2012 Summary of Changes Notes ...
Page 228: ...228 RockwellAutomationPublication290E UM001B EN P June2012 Appendix B CIP Information Notes ...
Page 251: ......