112
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
Starter Protection Group
OLResetLevel
This parameter determines the % Thermal
Capacity which an overload can be cleared.
Parameter Number
29
Access Rule
GET/SET
Data Type
BYTE
Group
Basic Configuration
Units
% TCU
Minimum Value
75
Maximum Value
100
Default Value
75
OverloadClass
This parameter provides the overload trip
classification.
1 = 10
2 = 15
3 = 20
Parameter Number
30
Access Rule
GET
Data Type
USINT
Group
Basic Configuration
Units
—
Minimum Value
1
Maximum Value
3
Default Value
1
ProtFltResetMode
This parameter configures the Protection
Fault reset mode.
0 = Manual
1 = Automatic
Parameter Number
41
Access Rule
GET/SET
Data Type
BOOL
Group
Starter Protection
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
TripStatus
This parameter provides the fault
condition that caused any current trip.
Parameter Number
42
Access Rule
GET
Data Type
WORD
Group
Trip Status
Units
—
Minimum Value
0
Maximum Value
0xE3BF
Default Value
0