Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
147
Bulletin 290E/291E/294E Programmable Parameters
Chapter
4
MotorOLRetention
Enables/disables the Motor overload
Retention function. When Enabled, the
value held in the motor overload counter
is saved at power-down and restored
at power-up. A change to this parameter
setting resets the counter.
0 = Disabled (Default)
1 = Enabled
Parameter Number
71
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
—
Minimum Value
0
Maximum Value
1
Default Value
0
InternalFreq
Provide the frequency command to drive
when Parameter 33 (Speed-Reference) =
1 (InternalFreq). When enabled, this
parameter will change the frequency
command in real time.
Parameter Number
72
Related Parameters
33
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x Hz
Minimum Value
0.0
Maximum Value
400.0
Default Value
60.0
SkipFrequency
Sets the frequency at which the drive will
not operate.
Parameter Number
73
Related Parameters
74
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
Hz
Minimum Value
0
Maximum Value
400 Hz
Default Value
0 Hz
SkipFrqBand
Determines the band width around
Parameter 73 (SkipFrequency). Parameter
74 (SkipFreqBand) is split applying 1/2
above and 1/2 below the actual skip
frequency. A setting of 0.0 disables
this parameter.
Parameter Number
74
Related Parameters
73
Access Rule
GET/SET
Data Type
UINT
Group
Advanced Config.
Units
x.x Hz
Minimum Value
0.0 Hz
Maximum Value
30.0 Hz
Default Value
0.0 Hz