122
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
JamWarningLevel
This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.
Parameter Number
73
Access Rule
GET
Data Type
UINT
Group
Advanced Config.
Units
%FLA
Minimum Value
50
Maximum Value
600
Default Value
150
StallEnabledTime
This parameter determines the time
that stall detection is enabled during
motor starting.
Parameter Number
74
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
secs
Minimum Value
0
Maximum Value
250
Default Value
10
StallTripLevel
This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.
Parameter Number
75
Access Rule
GET
Data Type
UINT
Group
Advanced Config.
Units
%FLA
Minimum Value
100
Maximum Value
600
Default Value
600
ULInhibitTime
This parameter determines the time
during motor starting that Underload
detection is inhibited.
Parameter Number
76
Access Rule
GET
Data Type
USINT
Group
Advanced Config.
Units
secs
Minimum Value
0
Maximum Value
250
Default Value
10